Ring Main Unit · CSG O
SF6-Insulated Outdoor Ring Main Unit
For secondary distribution points outside conventional switchrooms, C-SEC lists an outdoor SF6-insulated RMU product family. Correct specification begins with the electrical scheme and the environmental conditions in which the equipment must operate.
CSG O on mounting frame · catalogue photograph01
Practical installation needs
Outdoor RMU selection involves equipment protection, accessible switching, safe separation, civil foundations, cable routing and service access. Those site parameters are as important as the core electrical ratings.
02
Network applications
Use an approved schematic to demonstrate ring feeder switching, transformer protection and possible automation functions within the specific product lineup.
03
Environmental qualification
Publish actual IP and environmental/temperature data, not generalized claims such as 'weatherproof under all conditions.'
04
Testing and documentation
Explain what type-test and routine-test evidence is available for the model and how a buyer can request it.
05
Next step
Share your outdoor site requirements and single-line diagram with C-SEC's engineering team.
Features
General characteristics
- 01SF6-insulated compact switchgear
- 02Equipped with SF6 switch disconnector
- 03Equipped with vacuum circuit breaker
- 04Modular or compact versions
- 05Internal arc resistant
- 06SCADA-compatible motorised unit, on request
- 07Stainless steel tank
- 08Developed according to IEC 62271-200
As listed in the C-SEC MV Switchgear Catalogue (2022).
Typical functions · 2 LBS + 1 CB
Select a unit
Typical arrangement drawn from the catalogue's typical functions. Your project configuration comes from the network SLD.
Available modules (catalogue): LBS · CB · M
Specifications
Technical data
Catalogue model · CSG O
| Characteristic | Unit | 12 kV | 17.5 kV |
|---|---|---|---|
| Electrical data | |||
| Rated voltage | kV | 12 | 17.5 |
| Lightning impulse withstand (1.2/50 µs) | kV peak | 75 | 95 |
| Power-frequency withstand (50 Hz, 1 min) | kV rms | 28 | 38 |
| Rated current | A | 630 | 630 |
| Rated short-time current | kA rms | 21 (3 s) | 21 (3 s) |
| Short-circuit making current | kA peak | 52.5 | 52.5 |
| Mechanical & service | |||
| Protection degree | — | RMU IP54 · Tank IP67 | |
| Standard colour | — | RAL 7012 | |
| Ambient temperature | °C | Basic −5 … +40; option −10 … +55 | |
| Dimensions (2 LBS + 1 CB) | |||
| Height | mm | 1755 | |
| Width | mm | 840 | |
| Depth | mm | 1125 | |
Source: C-SEC Medium Voltage Switchgear Catalogue (2022, QMS/FRM/SDM/72-04 R2 Issue 05). Technical characteristics vary by model and project configuration — refer to the latest approved C-SEC datasheet.
Documents
Technical documents
Only approved files are published. Project-specific documents are shared on request.
- Download
PDF · 2.2 MB · Rev. R2 Issue 05
MV Switchgear Catalogue (2022)
- Request for your configuration →
On request
Product datasheet
- Request for your configuration →
On request
GA / footprint drawing
- Request for your configuration →
On request
Typical SLD
- Request for your configuration →
On request
Installation prerequisites
- Request for your configuration →
On request
Test / standards declaration
Questions about the Outdoor SF6 RMU
Civil interface requirements depend on the supplied enclosure and approved GA.
Only validated, supported variants should be described as motorisable.
Enquiry
Project-specific quotation
Share the key electrical parameters and the required panel functions for a technical review.
Typical applications
Related equipment
CSG I12 kV · 24 kV
Indoor SF6 RMU
Compact SF6-insulated switchgear for suitable indoor secondary distribution installations.
View technical details →
CSG IK12 kV · 17.5 kV
Indoor/Outdoor SF6 RMU
An RMU category for projects where installation conditions call for indoor and outdoor use.
View technical details →
- 33 kV
33 kV
33 kV RMU
C-SEC's first 33 kV RMU, manufactured at Haridwar under licence from Ormazabal, Spain, has been commissioned in Maharashtra.
View technical details →